MCC4_AS4
Controller • BACnet/IP (native) Data via BMS sub-network
FAT: Not StartedSAT: Not StartedCBN: Pending
Device Information
- Device ID
- MCC4_AS4
- Sub-System
- BMS
- Role
- Controller
- Protocol
- BACnet/IP (native) Data via BMS sub-network
Schneider Electric AS-P (Automation Server)
Testing Status
FAT StatusNot Started
SAT StatusNot Started
CBN OnboardedPending
Security Checklist
Encryption in Transit
Default Credentials Removed
Read-Only Interface
Total Points
94
Verified
0
Failed
0
Not Tested
94
Points Register (94 points)
Online· 11:31
Showing 94 of 94 points
| Point | Full Nomenclature | Equipment | Data Type | Status |
|---|---|---|---|---|
Common Chilled Water Return Temperature Common · | 4 Brandon Road-BMS-Common-ComChwRetTmp | Common — | Analog | Required |
RF2 HWS ASHP Fault RF · | 4 Brandon Road-BMS-RF-02-RF2HwsAshpFlt | RF-02 — | Digital | Required |
PRF9 LTHW Secondary Pump Flow P · | 4 Brandon Road-BMS-P-RF-09-PRF9LthwSecPmpFlw | P-RF-09 — | Digital | Required |
LTHW Pump Fault LTHW · | 4 Brandon Road-BMS-LTHW-LthwPuFlt | LTHW — | Digital | Required |
PRF4 CHW Secondary Pump Control P · | 4 Brandon Road-BMS-P-RF-04-PRF4ChwSecPmpCtl | P-RF-04 — | Analog | Required |
Outside Air Temperature External · | 4 Brandon Road-BMS-External-OaTmp | External — | Analog | Required |
P R F9 Lthw Ret Tmp P · | 4 Brandon Road-BMS-P-RF-09/10-PRF9LthwRetTmp | P-RF-09/10 — | Analog | Required |
P R F6 Vt Pmp Ctl P · | 4 Brandon Road-BMS-P-RF-06-PRF6VtPmpCtl | P-RF-06 — | Analog | Required |
R F1 As Chw Ret Tmp RF · | 4 Brandon Road-BMS-RF-01/2-RF1AsChwRetTmp | RF-01/2 — | Analog | Required |
P R F3 Chw Flw Tmp P · | 4 Brandon Road-BMS-P-RF-03/4-PRF3ChwFlwTmp | P-RF-03/4 — | Analog | Required |
Vt Vlv Ctl VT · | 4 Brandon Road-BMS-VT-VtVlvCtl | VT — | Analog | Required |
P R F5 Vt Sec Pmp Flt P · | 4 Brandon Road-BMS-P-RF-05-PRF5VtSecPmpFlt | P-RF-05 — | Digital | Required |
P R F1 Chw Sec Pmp Ena P · | 4 Brandon Road-BMS-P-RF-01-PRF1ChwSecPmpEna | P-RF-01 — | AV | Required |
R F1 Hws Ashp Flt RF · | 4 Brandon Road-BMS-RF-01-RF1HwsAshpFlt | RF-01 — | Digital | Required |
P R F7 Lthw Prs P · | 4 Brandon Road-BMS-P-RF-07/8-PRF7LthwPrs | P-RF-07/8 — | Analog | Required |
P R F1 Lthw Flw Tmp P · | 4 Brandon Road-BMS-P-RF-01/2-PRF1LthwFlwTmp | P-RF-01/2 — | Analog | Required |
Lthw Buff Tmp LTHW · | 4 Brandon Road-BMS-LTHW-LthwBuffTmp | LTHW — | Analog | Required |
P R F9 Lthw Sec Pmp Flt P · | 4 Brandon Road-BMS-P-RF-09-PRF9LthwSecPmpFlt | P-RF-09 — | Digital | Required |
Sct Safety · | 4 Brandon Road-BMS-Safety-Sct | Safety — | Analog | Required |
P R F5 Vt Sec Pmp Ena P · | 4 Brandon Road-BMS-P-RF-05-PRF5VtSecPmpEna | P-RF-05 — | AV | Required |
P R F2 Chw Sec Pmp Flw P · | 4 Brandon Road-BMS-P-RF-02-PRF2ChwSecPmpFlw | P-RF-02 — | Digital | Required |
Com Lthw Flw Tmp Common · | 4 Brandon Road-BMS-Common-ComLthwFlwTmp | Common — | Analog | Required |
Com Lthw Ret Tmp Common · | 4 Brandon Road-BMS-Common-ComLthwRetTmp | Common — | Analog | Required |
P R F3 Chw Sec Pmp Flw P · | 4 Brandon Road-BMS-P-RF-03-PRF3ChwSecPmpFlw | P-RF-03 — | Digital | Required |
PRF 7 Lthw Flow Temperature P · | 4 Brandon Road-BMS-P-RF-07/8-PRF7LthwFlwTmp | P-RF-07/8 — | Analog | Required |
PRF 1 Chilled Water Secondary Pump Control P · | 4 Brandon Road-BMS-P-RF-01-PRF1ChwSecPmpCtl | P-RF-01 — | Analog | Required |
PRF 7 Lthw Secondary Pump Enable P · | 4 Brandon Road-BMS-P-RF-07-PRF7LthwSecPmpEna | P-RF-07 — | AV | Required |
Chilled Water Buff Temperature CHW · | 4 Brandon Road-BMS-CHW-ChwBuffTmp | CHW — | Analog | Required |
PRF 5 Vt Flow Temperature P · | 4 Brandon Road-BMS-P-RF-05/6-PRF5VtFlwTmp | P-RF-05/6 — | Analog | Required |
Chilled Water Pu Fault CHW · | 4 Brandon Road-BMS-CHW-ChwPuFlt | CHW — | Digital | Required |
PRF 2 Chilled Water Secondary Pump Control P · | 4 Brandon Road-BMS-P-RF-02-PRF2ChwSecPmpCtl | P-RF-02 — | Analog | Required |
RF 1 As Chilled Water Flow Temperature RF · | 4 Brandon Road-BMS-RF-01/2-RF1AsChwFlwTmp | RF-01/2 — | Analog | Required |
PRF 2 Chilled Water Secondary Pump Fault P · | 4 Brandon Road-BMS-P-RF-02-PRF2ChwSecPmpFlt | P-RF-02 — | Digital | Required |
PRF 9 Lthw Flow Temperature P · | 4 Brandon Road-BMS-P-RF-09/10-PRF9LthwFlwTmp | P-RF-09/10 — | Analog | Required |
Lthw Ss Fil Fault LTHW · | 4 Brandon Road-BMS-LTHW-LthwSsFilFlt | LTHW — | Digital | Required |
PRF 3 Chilled Water Secondary Pump Fault P · | 4 Brandon Road-BMS-P-RF-03-PRF3ChwSecPmpFlt | P-RF-03 — | Digital | Required |
PRF 8 Lthw Secondary Pump Fault P · | 4 Brandon Road-BMS-P-RF-08-PRF8LthwSecPmpFlt | P-RF-08 — | Digital | Required |
W Meter RF 03 WM · | 4 Brandon Road-BMS-WM-RF-03-WMtrRF-03 | WM-RF-03 — | Analog | Required |
PRF 7 Lthw Secondary Pump Fault P · | 4 Brandon Road-BMS-P-RF-07-PRF7LthwSecPmpFlt | P-RF-07 — | Digital | Required |
PRF 5 Vt Return Temperature P · | 4 Brandon Road-BMS-P-RF-05/6-PRF5VtRetTmp | P-RF-05/6 — | Analog | Required |
PRF 10 Lthw Secondary Pump Flow P · | 4 Brandon Road-BMS-P-RF-10-PRF10LthwSecPmpFlw | P-RF-10 — | Digital | Required |
PRF 1 Chilled Water Prs P · | 4 Brandon Road-BMS-P-RF-01/2-PRF1ChwPrs | P-RF-01/2 — | Analog | Required |
W Meter RF 02 WM · | 4 Brandon Road-BMS-WM-RF-02-WMtrRF-02 | WM-RF-02 — | Analog | Required |
PRF 8 Lthw Secondary Pump Flow P · | 4 Brandon Road-BMS-P-RF-08-PRF8LthwSecPmpFlw | P-RF-08 — | Digital | Required |
PRF 7 Lthw Return Temperature P · | 4 Brandon Road-BMS-P-RF-07/8-PRF7LthwRetTmp | P-RF-07/8 — | Analog | Required |
Thtg Fault Trace · | 4 Brandon Road-BMS-Trace-ThtgFlt | Trace — | Analog | Required |
PRF 6 Vt Secondary Pump Enable P · | 4 Brandon Road-BMS-P-RF-06-PRF6VtSecPmpEna | P-RF-06 — | AV | Required |
PRF 7 Lthw Secondary Pump Flow P · | 4 Brandon Road-BMS-P-RF-07-PRF7LthwSecPmpFlw | P-RF-07 — | Digital | Required |
PRF 4 Chilled Water Secondary Pump Enable P · | 4 Brandon Road-BMS-P-RF-04-PRF4ChwSecPmpEna | P-RF-04 — | AV | Required |
Falm Fire · | 4 Brandon Road-BMS-Fire-Falm | Fire — | Analog | Required |
PRF 6 Vt Secondary Pump Flow P · | 4 Brandon Road-BMS-P-RF-06-PRF6VtSecPmpFlw | P-RF-06 — | Digital | Required |
Lthw Ashp Seq Enable LTHW · | 4 Brandon Road-BMS-LTHW-LthwAshpSeqEna | LTHW — | AV | Required |
PRF 5 Vt Prs P · | 4 Brandon Road-BMS-P-RF-05/6-PRF5VtPrs | P-RF-05/6 — | Analog | Required |
RF 2 Ashp Fault RF · | 4 Brandon Road-BMS-RF-02-RF2AshpFlt | RF-02 — | Digital | Required |
PRF 8 Lthw Secondary Pump Enable P · | 4 Brandon Road-BMS-P-RF-08-PRF8LthwSecPmpEna | P-RF-08 — | AV | Required |
PRF 1 Lthw Prs P · | 4 Brandon Road-BMS-P-RF-01/2-PRF1LthwPrs | P-RF-01/2 — | Analog | Required |
PRF 10 Lthw Secondary Pump Enable P · | 4 Brandon Road-BMS-P-RF-10-PRF10LthwSecPmpEna | P-RF-10 — | Digital | Required |
PRF 3 Chilled Water Secondary Pump Enable P · | 4 Brandon Road-BMS-P-RF-03-PRF3ChwSecPmpEna | P-RF-03 — | AV | Required |
PRF 8 Lthw Secondary Pump Control P · | 4 Brandon Road-BMS-P-RF-08-PRF8LthwSecPmpCtl | P-RF-08 — | Analog | Required |
Lthw Ss Fil Status LTHW · | 4 Brandon Road-BMS-LTHW-LthwSsFilSts | LTHW — | Digital | Required |
Lthw Pu Status LTHW · | 4 Brandon Road-BMS-LTHW-LthwPuSts | LTHW — | Digital | Required |
PRF 7 Lthw Secondary Pump Control P · | 4 Brandon Road-BMS-P-RF-07-PRF7LthwSecPmpCtl | P-RF-07 — | Analog | Required |
PRF 6 Vt Secondary Pump Fault P · | 4 Brandon Road-BMS-P-RF-06-PRF6VtSecPmpFlt | P-RF-06 — | Digital | Required |
RF 12 Hot Water Ashp Enable RF · | 4 Brandon Road-BMS-RF-02-RF12HwsAshpEna | RF-02 — | AV | Required |
RF 1 Hot Water Ashp Enable RF · | 4 Brandon Road-BMS-RF-01-RF1HwsAshpEna | RF-01 — | AV | Required |
PRF 9 Lthw Secondary Pump Control P · | 4 Brandon Road-BMS-P-RF-09-PRF9LthwSecPmpCtl | P-RF-09 — | Analog | Required |
PRF 1 Lthw Return Temperature P · | 4 Brandon Road-BMS-P-RF-01/2-PRF1LthwRetTmp | P-RF-01/2 — | Analog | Required |
PRF 3 Chilled Water Prs P · | 4 Brandon Road-BMS-P-RF-03/4-PRF3ChwPrs | P-RF-03/4 — | Analog | Required |
PRF 10 Lthw Secondary Pump Control P · | 4 Brandon Road-BMS-P-RF-10-PRF10LthwSecPmpCtl | P-RF-10 — | Analog | Required |
RF 1 As Lthw Return Temperature RF · | 4 Brandon Road-BMS-RF-01/2-RF1AsLthwRetTmp | RF-01/2 — | Analog | Required |
W Meter RF 04 WM · | 4 Brandon Road-BMS-WM-RF-04-WMtrRF-04 | WM-RF-04 — | Analog | Required |
PRF 4 Chilled Water Secondary Pump Fault P · | 4 Brandon Road-BMS-P-RF-04-PRF4ChwSecPmpFlt | P-RF-04 — | Digital | Required |
PRF 3 Chilled Water Return Temperature P · | 4 Brandon Road-BMS-P-RF-03/4-PRF3ChwRetTmp | P-RF-03/4 — | Analog | Required |
Chilled Water Ss Fil Status CHW · | 4 Brandon Road-BMS-CHW-ChwSsFilSts | CHW — | Digital | Required |
PRF 10 Lthw Secondary Pump Fault P · | 4 Brandon Road-BMS-P-RF-10-PRF10LthwSecPmpFlt | P-RF-10 — | Digital | Required |
Com Chilled Water Flow Temperature Common · | 4 Brandon Road-BMS-Common-ComChwFlwTmp | Common — | Analog | Required |
Chilled Water Ashp Seq Enable CHW · | 4 Brandon Road-BMS-CHW-ChwAshpSeqEna | CHW — | AV | Required |
Oa Humidity External · | 4 Brandon Road-BMS-External-OaHum | External — | Analog | Required |
W Meter RF 01 WM · | 4 Brandon Road-BMS-WM-RF-01-WMtrRF-01 | WM-RF-01 — | Analog | Required |
PRF 2 Lthw Secondary Pump Enable P · | 4 Brandon Road-BMS-P-RF-02-PRF2LthwSecPmpEna | P-RF-02 — | AV | Required |
PRF 1 Chilled Water Return Temperature P · | 4 Brandon Road-BMS-P-RF-01/2-PRF1ChwRetTmp | P-RF-01/2 — | Analog | Required |
PRF 5 Vt Secondary Pump Flow P · | 4 Brandon Road-BMS-P-RF-04-PRF5VtSecPmpFlw | P-RF-04 — | Digital | Required |
Chilled Water Ss Fil Fault CHW · | 4 Brandon Road-BMS-CHW-ChwSsFilFlt | CHW — | Digital | Required |
PRF 3 Chilled Water Secondary Pump Control P · | 4 Brandon Road-BMS-P-RF-03-PRF3ChwSecPmpCtl | P-RF-03 — | Analog | Required |
PRF 1 Chilled Water Flow Temperature P · | 4 Brandon Road-BMS-P-RF-01/2-PRF1ChwFlwTmp | P-RF-01/2 — | Analog | Required |
PRF 1 Chilled Water Secondary Pump Fault P · | 4 Brandon Road-BMS-P-RF-01-PRF1ChwSecPmpFlt | P-RF-01 — | Digital | Required |
PRF 5 Vt Pump Control P · | 4 Brandon Road-BMS-P-RF-05-PRF5VtPmpCtl | P-RF-05 — | Analog | Required |
RF 1 Ashp Fault RF · | 4 Brandon Road-BMS-RF-01-RF1AshpFlt | RF-01 — | Digital | Required |
Chilled Water Pu Status CHW · | 4 Brandon Road-BMS-CHW-ChwPuSts | CHW — | Digital | Required |
PRF 4 Chilled Water Secondary Pump Flow P · | 4 Brandon Road-BMS-P-RF-04-PRF4ChwSecPmpFlw | P-RF-04 — | Digital | Required |
PRF 9 Lthw Prs P · | 4 Brandon Road-BMS-P-RF-09/10-PRF9LthwPrs | P-RF-09/10 — | Analog | Required |
PRF 1 Chilled Water Secondary Pump Flow P · | 4 Brandon Road-BMS-P-RF-01-PRF1ChwSecPmpFlw | P-RF-01 — | Digital | Required |
RF 1 As Lthw Flow Temperature RF · | 4 Brandon Road-BMS-RF-01/2-RF1AsLthwFlwTmp | RF-01/2 — | Analog | Required |
PRF 9 Lthw Secondary Pump Enable P · | 4 Brandon Road-BMS-P-RF-09-PRF9LthwSecPmpEna | P-RF-09 — | Digital | Required |