MCC7_AS7
Controller • BACnet/IP (native) Data via BMS sub-network
FAT: Not StartedSAT: Not StartedCBN: Pending
Device Information
- Device ID
- MCC7_AS7
- Sub-System
- BMS
- Role
- Controller
- Protocol
- BACnet/IP (native) Data via BMS sub-network
Schneider Electric AS-P (Automation Server)
Testing Status
FAT StatusNot Started
SAT StatusNot Started
CBN OnboardedPending
Security Checklist
Encryption in Transit
Default Credentials Removed
Read-Only Interface
Total Points
33
Verified
0
Failed
0
Not Tested
33
Points Register (33 points)
Online· 08:49
Showing 33 of 33 points
| Point | Full Nomenclature | Equipment | Data Type | Status |
|---|---|---|---|---|
AHU RF04 Inlet Temperature AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRF04InTmp | AHU-RF-04 — | Analog | Required |
Ahu Rf04 Sup Prs AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04SupPrs | AHU-RF-04 — | Analog | Required |
Gen Low Fuel Alm Generator · | 4 Brandon Road-BMS-Generator-GenLowFuelAlm | Generator — | Digital | Required |
Ahu Rf04 Fstat AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04Fstat | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 In Dpr Opn AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04InDprOpn | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Cc Valve Fbk AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04CcVlvFbk | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Rcr Dpr Opn AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04RcrDprOpn | AHU-RF-04 — | Digital | Required |
Gen Com Alarm Generator · | 4 Brandon Road-BMS-Generator-GenComAlm | Generator — | Digital | Required |
Air Handling Unit Rf 04 Fc Valve Fbk AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04FcVlvFbk | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Eha Dpr Opn AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04EhaDprOpn | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Cc Valve Control AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04CcVlvCtl | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Panel Fil Status AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04PanFilSts | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Ext Prs AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04ExtPrs | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Supply Fan Speed AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04SupFanSpd | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Ext Fan Fault AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04ExtFanFlt | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Supply Fan Enable AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04SupFanEna | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Supply Humidity AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04SupHum | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Supply Temperature AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04SupTmp | AHU-RF-04 — | Analog | Required |
Falm Fire · | 4 Brandon Road-BMS-Fire-Falm | Fire — | Digital | Required |
Air Handling Unit Rf 04 In Eha Dpr Enable AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04InEhaDprEna | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Ext Fan Flow AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04ExtFanFlw | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Ext Fan Speed AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04ExtFanSpd | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Rcr Dpr Enable AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04RcrDprEna | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Ext Temperature AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04ExtTmp | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Bag Fil Status AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04BagFilSts | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Fc Valve Control AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04FcVlvCtl | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Supply Fan Fault AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04SupFanFlt | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Supply Fan Flow AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04SupFanFlw | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Hc Valve Fbk AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04HcVlvFbk | AHU-RF-04 — | Analog | Required |
Air Handling Unit Rf 04 Ext Fan Enable AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04ExtFanEna | AHU-RF-04 — | Digital | Required |
Air Handling Unit Rf 04 Rcr Dpr Cls AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04RcrDprCls | AHU-RF-04 — | Digital | Required |
Gen Running Status Generator · | 4 Brandon Road-BMS-Generator-GenRunSts | Generator — | Digital | Required |
Air Handling Unit Rf 04 Hc Valve Control AHU · | 4 Brandon Road-BMS-AHU-RF-04-AhuRf04HcVlvCtl | AHU-RF-04 — | Analog | Required |