MCC1_AS1

ControllerBACnet/IP (native) Data via BMS sub-network

FAT: Not StartedSAT: Not StartedCBN: Pending

Device Information

Device ID
MCC1_AS1
Sub-System
BMS
Role
Controller
Protocol
BACnet/IP (native) Data via BMS sub-network

Schneider Electric AS-P (Automation Server)

Testing Status

FAT StatusNot Started
SAT StatusNot Started
CBN OnboardedPending

Security Checklist

Encryption in Transit
Default Credentials Removed
Read-Only Interface
Total Points
65
Verified
0
Failed
0
Not Tested
65

Points Register (65 points)

Online· 11:35
Showing 65 of 65 points
PointFull NomenclatureEquipmentData TypeStatus
End of Line Bypass Valve
EOL ·
4 Brandon Road-BMS-EOL-EOLBypassValve
EOL
AnalogRequired
Extract Fan B101 External Fan
EF · B1
4 Brandon Road-B1-01-BMS-EF-B1-01-EFB101ExtFan
EF-B1-01
01
DigitalRequired
AHU B103 External Temperature
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtTemp
AHU-B1-03
03
AnalogRequired
A H U B103 Sup Dmp C
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupDmpC
AHU-B1-03
03
DigitalRequired
A H U B103 Sup Speed
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupSpeed
AHU-B1-03
03
AnalogRequired
M S F D1 Open
Basement ·
4 Brandon Road-BMS-Basement-MSFD1Open
Basement
DigitalRequired
A H U B103 Frost Vlv
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103FrostVlv
AHU-B1-03
03
AnalogRequired
A H U B103 Ext Press
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtPress
AHU-B1-03
03
AnalogRequired
A H U B103 Frost
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103Frost
AHU-B1-03
03
DigitalRequired
A H U B103 Sup Dmp O
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupDmpO
AHU-B1-03
03
DigitalRequired
A H U B103 Heat Vlv
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103HeatVlv
AHU-B1-03
03
AnalogRequired
A H U B103 Ext Speed
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtSpeed
AHU-B1-03
03
AnalogRequired
AHUB 103 Supply Damper
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupDmp
AHU-B1-03
03
DigitalRequired
EF 0001 Ext Fault
EF · 00
4 Brandon Road-00-01-BMS-EF-00-01-EF0001ExtFlt
EF-00-01
01
DigitalRequired
AHUB 103 Ext Damper
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtDmp
AHU-B1-03
03
DigitalRequired
AHUB 103 Clg Valve
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ClgVlv
AHU-B1-03
03
AnalogRequired
MER Refrig Alarm
MER ·
4 Brandon Road-Mer Room-BMS-MER-MERRefrigAlm
MER
Mer Room
DigitalRequired
AHUB 103 Frost Valve
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103FrostVlv
AHU-B1-03
03
AnalogRequired
DX Unit 1
DX ·
4 Brandon Road-BMS-DX-UNIT-1-DXUnit1
DX-UNIT-1
DigitalRequired
MSFD 4 Open
Basement ·
4 Brandon Road-BMS-Basement-MSFD4Open
Basement
DigitalRequired
AHUB 103 Recoup C
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103RecoupC
AHU-B1-03
03
DigitalRequired
AHUB 103 Inlet Temperature
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103InletTemp
AHU-B1-03
03
AnalogRequired
Smoke Fans Running
Smoke ·
4 Brandon Road-BMS-Smoke-SmokeFansRun
Smoke
AnalogRequired
AHUB 103 Supply Flow
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupFlow
AHU-B1-03
03
DigitalRequired
AHUB 103 Ext Fan
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtFan
AHU-B1-03
03
DigitalRequired
MSFD 3 Open
Basement ·
4 Brandon Road-BMS-Basement-MSFD3Open
Basement
DigitalRequired
MSFD 7 Open
Basement ·
4 Brandon Road-BMS-Basement-MSFD7Open
Basement
DigitalRequired
AHUB 103 Recoup O
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103RecoupO
AHU-B1-03
03
DigitalRequired
DX Unit 4 Fault
DX ·
4 Brandon Road-BMS-DX-UNIT-4-DXUnit4Flt
DX-UNIT-4
DigitalRequired
ATS 2 Status
ATS ·
4 Brandon Road-BMS-ATS-ATS2Status
ATS
AnalogRequired
DX Unit 4
DX ·
4 Brandon Road-BMS-DX-UNIT-4-DXUnit4
DX-UNIT-4
DigitalRequired
DX Unit 3 Fault
DX ·
4 Brandon Road-BMS-DX-UNIT-3-DXUnit3Flt
DX-UNIT-3
DigitalRequired
AHUB 103 Supply Fault
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupFlt
AHU-B1-03
03
DigitalRequired
ATS 3 Status
ATS ·
4 Brandon Road-BMS-ATS-ATS3Status
ATS
AnalogRequired
MSFD 8 Open
Basement ·
4 Brandon Road-BMS-Basement-MSFD8Open
Basement
DigitalRequired
EF 0001 Ext Fan
EF · 00
4 Brandon Road-00-01-BMS-EF-00-01-EF0001ExtFan
EF-00-01
01
DigitalRequired
Foul Water Pump Fault
Foul ·
4 Brandon Road-BMS-Foul-FoulWtrPumpFlt
Foul
DigitalRequired
AHUB 103 Ext Flow
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtFlow
AHU-B1-03
03
DigitalRequired
MFSD Panel Status
MFSD ·
4 Brandon Road-BMS-MFSD-MFSDPanelSts
MFSD
DigitalRequired
MFSD Panel Fault
MFSD ·
4 Brandon Road-BMS-MFSD-MFSDPanelFlt
MFSD
DigitalRequired
AHUB 103 Supply Temperature
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupTemp
AHU-B1-03
03
AnalogRequired
EFB 101 Ext Fault
EF · B1
4 Brandon Road-B1-01-BMS-EF-B1-01-EFB101ExtFlt
EF-B1-01
01
DigitalRequired
DX Unit 2
DX ·
4 Brandon Road-BMS-DX-UNIT-2-DXUnit2
DX-UNIT-2
DigitalRequired
EOL Pressure
EOL ·
4 Brandon Road-BMS-EOL-EOLPressure
EOL
AnalogRequired
MSFD 5 Open
Basement ·
4 Brandon Road-BMS-Basement-MSFD5Open
Basement
DigitalRequired
Foul Water Pump Running
Foul ·
4 Brandon Road-BMS-Foul-FoulWtrPumpRun
Foul
DigitalRequired
EOL Bypass Valve
EOL ·
4 Brandon Road-BMS-EOL-EOLBypassVlv
EOL
AnalogRequired
AHUB 103 Supply Humidity
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupHum
AHU-B1-03
03
AnalogRequired
MSFD 6 Open
Basement ·
4 Brandon Road-BMS-Basement-MSFD6Open
Basement
DigitalRequired
DX Unit 1 Fault
DX ·
4 Brandon Road-BMS-DX-UNIT-1-DXUnit1Flt
DX-UNIT-1
DigitalRequired
AHUB 103 Bag Drty
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103BagDrty
AHU-B1-03
03
DigitalRequired
Fire Alarm
Fire ·
4 Brandon Road-BMS-Fire-FireAlarm
Fire
DigitalRequired
AHUB 103 Panel Drty
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103PanelDrty
AHU-B1-03
03
DigitalRequired
AHUB 103 Recoup Damper
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103RecoupDmp
AHU-B1-03
03
DigitalRequired
AHUB 103 Supply Press
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupPress
AHU-B1-03
03
AnalogRequired
AHUB 103 Supply Fan
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupFan
AHU-B1-03
03
DigitalRequired
AHUB 103 Clg Valve
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ClgVlv
AHU-B1-03
03
AnalogRequired
ATS 1 Status
ATS ·
4 Brandon Road-BMS-ATS-ATS1Status
ATS
AnalogRequired
MSFD 2 Open
Basement ·
4 Brandon Road-BMS-Basement-MSFD2Open
Basement
DigitalRequired
MER Space Temperature
MER ·
4 Brandon Road-BMS-MER-MERSpaceTemp
MER
AnalogRequired
Gas Detector Alarm
Gas ·
4 Brandon Road-BMS-Gas-GasDetAlm
Gas
DigitalRequired
AHUB 103 Heat Valve
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103HeatVlv
AHU-B1-03
03
AnalogRequired
DX Unit 2 Fault
DX ·
4 Brandon Road-BMS-DX-UNIT-2-DXUnit2Flt
DX-UNIT-2
DigitalRequired
AHUB 103 Ext Fault
AHU · B1
4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtFlt
AHU-B1-03
03
DigitalRequired
DX Unit 3
DX ·
4 Brandon Road-BMS-DX-UNIT-3-DXUnit3
DX-UNIT-3
DigitalRequired