MCC1_AS1
Controller • BACnet/IP (native) Data via BMS sub-network
FAT: Not StartedSAT: Not StartedCBN: Pending
Device Information
- Device ID
- MCC1_AS1
- Sub-System
- BMS
- Role
- Controller
- Protocol
- BACnet/IP (native) Data via BMS sub-network
Schneider Electric AS-P (Automation Server)
Testing Status
FAT StatusNot Started
SAT StatusNot Started
CBN OnboardedPending
Security Checklist
Encryption in Transit
Default Credentials Removed
Read-Only Interface
Total Points
65
Verified
0
Failed
0
Not Tested
65
Points Register (65 points)
Online· 11:35
Showing 65 of 65 points
| Point | Full Nomenclature | Equipment | Data Type | Status |
|---|---|---|---|---|
End of Line Bypass Valve EOL · | 4 Brandon Road-BMS-EOL-EOLBypassValve | EOL — | Analog | Required |
Extract Fan B101 External Fan EF · B1 | 4 Brandon Road-B1-01-BMS-EF-B1-01-EFB101ExtFan | EF-B1-01 01 | Digital | Required |
AHU B103 External Temperature AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtTemp | AHU-B1-03 03 | Analog | Required |
A H U B103 Sup Dmp C AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupDmpC | AHU-B1-03 03 | Digital | Required |
A H U B103 Sup Speed AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupSpeed | AHU-B1-03 03 | Analog | Required |
M S F D1 Open Basement · | 4 Brandon Road-BMS-Basement-MSFD1Open | Basement — | Digital | Required |
A H U B103 Frost Vlv AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103FrostVlv | AHU-B1-03 03 | Analog | Required |
A H U B103 Ext Press AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtPress | AHU-B1-03 03 | Analog | Required |
A H U B103 Frost AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103Frost | AHU-B1-03 03 | Digital | Required |
A H U B103 Sup Dmp O AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupDmpO | AHU-B1-03 03 | Digital | Required |
A H U B103 Heat Vlv AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103HeatVlv | AHU-B1-03 03 | Analog | Required |
A H U B103 Ext Speed AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtSpeed | AHU-B1-03 03 | Analog | Required |
AHUB 103 Supply Damper AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupDmp | AHU-B1-03 03 | Digital | Required |
EF 0001 Ext Fault EF · 00 | 4 Brandon Road-00-01-BMS-EF-00-01-EF0001ExtFlt | EF-00-01 01 | Digital | Required |
AHUB 103 Ext Damper AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtDmp | AHU-B1-03 03 | Digital | Required |
AHUB 103 Clg Valve AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ClgVlv | AHU-B1-03 03 | Analog | Required |
MER Refrig Alarm MER · | 4 Brandon Road-Mer Room-BMS-MER-MERRefrigAlm | MER Mer Room | Digital | Required |
AHUB 103 Frost Valve AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103FrostVlv | AHU-B1-03 03 | Analog | Required |
DX Unit 1 DX · | 4 Brandon Road-BMS-DX-UNIT-1-DXUnit1 | DX-UNIT-1 — | Digital | Required |
MSFD 4 Open Basement · | 4 Brandon Road-BMS-Basement-MSFD4Open | Basement — | Digital | Required |
AHUB 103 Recoup C AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103RecoupC | AHU-B1-03 03 | Digital | Required |
AHUB 103 Inlet Temperature AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103InletTemp | AHU-B1-03 03 | Analog | Required |
Smoke Fans Running Smoke · | 4 Brandon Road-BMS-Smoke-SmokeFansRun | Smoke — | Analog | Required |
AHUB 103 Supply Flow AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupFlow | AHU-B1-03 03 | Digital | Required |
AHUB 103 Ext Fan AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtFan | AHU-B1-03 03 | Digital | Required |
MSFD 3 Open Basement · | 4 Brandon Road-BMS-Basement-MSFD3Open | Basement — | Digital | Required |
MSFD 7 Open Basement · | 4 Brandon Road-BMS-Basement-MSFD7Open | Basement — | Digital | Required |
AHUB 103 Recoup O AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103RecoupO | AHU-B1-03 03 | Digital | Required |
DX Unit 4 Fault DX · | 4 Brandon Road-BMS-DX-UNIT-4-DXUnit4Flt | DX-UNIT-4 — | Digital | Required |
ATS 2 Status ATS · | 4 Brandon Road-BMS-ATS-ATS2Status | ATS — | Analog | Required |
DX Unit 4 DX · | 4 Brandon Road-BMS-DX-UNIT-4-DXUnit4 | DX-UNIT-4 — | Digital | Required |
DX Unit 3 Fault DX · | 4 Brandon Road-BMS-DX-UNIT-3-DXUnit3Flt | DX-UNIT-3 — | Digital | Required |
AHUB 103 Supply Fault AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupFlt | AHU-B1-03 03 | Digital | Required |
ATS 3 Status ATS · | 4 Brandon Road-BMS-ATS-ATS3Status | ATS — | Analog | Required |
MSFD 8 Open Basement · | 4 Brandon Road-BMS-Basement-MSFD8Open | Basement — | Digital | Required |
EF 0001 Ext Fan EF · 00 | 4 Brandon Road-00-01-BMS-EF-00-01-EF0001ExtFan | EF-00-01 01 | Digital | Required |
Foul Water Pump Fault Foul · | 4 Brandon Road-BMS-Foul-FoulWtrPumpFlt | Foul — | Digital | Required |
AHUB 103 Ext Flow AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtFlow | AHU-B1-03 03 | Digital | Required |
MFSD Panel Status MFSD · | 4 Brandon Road-BMS-MFSD-MFSDPanelSts | MFSD — | Digital | Required |
MFSD Panel Fault MFSD · | 4 Brandon Road-BMS-MFSD-MFSDPanelFlt | MFSD — | Digital | Required |
AHUB 103 Supply Temperature AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupTemp | AHU-B1-03 03 | Analog | Required |
EFB 101 Ext Fault EF · B1 | 4 Brandon Road-B1-01-BMS-EF-B1-01-EFB101ExtFlt | EF-B1-01 01 | Digital | Required |
DX Unit 2 DX · | 4 Brandon Road-BMS-DX-UNIT-2-DXUnit2 | DX-UNIT-2 — | Digital | Required |
EOL Pressure EOL · | 4 Brandon Road-BMS-EOL-EOLPressure | EOL — | Analog | Required |
MSFD 5 Open Basement · | 4 Brandon Road-BMS-Basement-MSFD5Open | Basement — | Digital | Required |
Foul Water Pump Running Foul · | 4 Brandon Road-BMS-Foul-FoulWtrPumpRun | Foul — | Digital | Required |
EOL Bypass Valve EOL · | 4 Brandon Road-BMS-EOL-EOLBypassVlv | EOL — | Analog | Required |
AHUB 103 Supply Humidity AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupHum | AHU-B1-03 03 | Analog | Required |
MSFD 6 Open Basement · | 4 Brandon Road-BMS-Basement-MSFD6Open | Basement — | Digital | Required |
DX Unit 1 Fault DX · | 4 Brandon Road-BMS-DX-UNIT-1-DXUnit1Flt | DX-UNIT-1 — | Digital | Required |
AHUB 103 Bag Drty AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103BagDrty | AHU-B1-03 03 | Digital | Required |
Fire Alarm Fire · | 4 Brandon Road-BMS-Fire-FireAlarm | Fire — | Digital | Required |
AHUB 103 Panel Drty AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103PanelDrty | AHU-B1-03 03 | Digital | Required |
AHUB 103 Recoup Damper AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103RecoupDmp | AHU-B1-03 03 | Digital | Required |
AHUB 103 Supply Press AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupPress | AHU-B1-03 03 | Analog | Required |
AHUB 103 Supply Fan AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103SupFan | AHU-B1-03 03 | Digital | Required |
AHUB 103 Clg Valve AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ClgVlv | AHU-B1-03 03 | Analog | Required |
ATS 1 Status ATS · | 4 Brandon Road-BMS-ATS-ATS1Status | ATS — | Analog | Required |
MSFD 2 Open Basement · | 4 Brandon Road-BMS-Basement-MSFD2Open | Basement — | Digital | Required |
MER Space Temperature MER · | 4 Brandon Road-BMS-MER-MERSpaceTemp | MER — | Analog | Required |
Gas Detector Alarm Gas · | 4 Brandon Road-BMS-Gas-GasDetAlm | Gas — | Digital | Required |
AHUB 103 Heat Valve AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103HeatVlv | AHU-B1-03 03 | Analog | Required |
DX Unit 2 Fault DX · | 4 Brandon Road-BMS-DX-UNIT-2-DXUnit2Flt | DX-UNIT-2 — | Digital | Required |
AHUB 103 Ext Fault AHU · B1 | 4 Brandon Road-B1-03-BMS-AHU-B1-03-AHUB103ExtFlt | AHU-B1-03 03 | Digital | Required |
DX Unit 3 DX · | 4 Brandon Road-BMS-DX-UNIT-3-DXUnit3 | DX-UNIT-3 — | Digital | Required |