EM-051
Other • Modbus RTU Integrated via BMS sub-network Exposed as BACnet/IP via BMS head-end
FAT: Not StartedSAT: Not StartedCBN: Pending
Device Information
- Device ID
- EM-051
- Sub-System
- Metering
- Role
- Other
- Protocol
- Modbus RTU Integrated via BMS sub-network Exposed as BACnet/IP via BMS head-end
Rayleigh Instruments RI-D360 DIN Rail Multifunction Meter
Testing Status
FAT StatusNot Started
SAT StatusNot Started
CBN OnboardedPending
Security Checklist
Encryption in Transit
Default Credentials Removed
Read-Only Interface
Total Points
14
Verified
0
Failed
0
Not Tested
14
Points Register (14 points)
Online· 11:31
Showing 14 of 14 points
| Point | Full Nomenclature | Equipment | Data Type | Status |
|---|---|---|---|---|
Alarm Status Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-AlarmStatus | EM-051 Roof LV Switchboard | Digital | Required |
Health Status Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-HealthStatus | EM-051 Roof LV Switchboard | Digital | Required |
Average Phase Voltage Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-AvgPhaseVoltage | EM-051 Roof LV Switchboard | Analog | Required |
CT Ratio Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-CTRatio | EM-051 Roof LV Switchboard | Analog | Required |
VT Ratio Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-VTRatio | EM-051 Roof LV Switchboard | Analog | Required |
Average Line Current Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-AvgLineCurrent | EM-051 Roof LV Switchboard | Analog | Required |
Total Reactive Power Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-TotalReactivePower | EM-051 Roof LV Switchboard | Analog | Required |
Cumulative Energy Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-CumulativeEnergy | EM-051 Roof LV Switchboard | Analog | Required |
Average Line Voltage Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-AvgLineVoltage | EM-051 Roof LV Switchboard | Analog | Required |
Cumulative Reactive Energy Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-CumulativeReactiveEnergy | EM-051 Roof LV Switchboard | Analog | Required |
Average Power Factor Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-AvgPowerFactor | EM-051 Roof LV Switchboard | Analog | Required |
AC Frequency Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-ACFrequency | EM-051 Roof LV Switchboard | Analog | Required |
Total Apparent Power Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-TotalApparentPower | EM-051 Roof LV Switchboard | Analog | Required |
Total Power Electric Meter · 05 | 4 Brandon Road-05-Roof LV Switchboard-Metering-EM-051-TotalPower | EM-051 Roof LV Switchboard | Analog | Required |